Voltage Detector Stick with air gap arrester for indoor use
Technical sheet
/ Standards
IEC 61235 / IEC 60855-1
/ Use

Stick for detecting the absence of voltage before earthing a line or a transformer to carry out work in MV substations or cells.

The detector's battery-free operation and built-in self-test make it possible, in indoor substations, to have a testing device that is always ready for use.

/ Technical specifications

TP13PM:

1 section insulating stick with a universal end fitting

Fibreglass composite tube, diameter 32 mm.

Operating voltage: 5 to 45 kV.

Test voltage on 300 mm: 50 kV.

Overall length: 1,50 m.

Weight: 600 g.

TR245U :

Telescopic insulating stick with a universal end fitting

Polyurethane foam-filled fibreglass composite upper tube, Ø 32 mm.

Fibreglass composite lower tube, Ø 39 mm.

Operating voltage: 25 to 63 kV kV.

Test voltage on 300 mm: 100 kV (upper section) / 50 KV (lower section).

Folded length: 0,85 m.

Extended length: 1,50 m.

Weight: 1,050 kg.

TDP536 : See next product description.

Product reference Weight (g) Longueur (m) Description Perche Technical sheet Quantity
TP13P 800 1,50 Perche fixe avec détecteur 5 à 36 kV TP13 PM
Pulse 32 Darkbg
TP13T 1350 0,85/1,50 Perche télescopique avec détecteur 5 - 36 kV TR245U
Pulse 32 Darkbg