Electrical shunt > TFK-TSF

TFK-TSF

Copper earthing cable
Technical sheet
/ Standards
Penta Bulletpoint CEI 61230
Penta Bulletpoint CEI 61138
/ Use
Provides copper connection between clamps and vices of portable earthing and short-circuiting devices.
Permissible short-circuit current is defined by cable cross-section and short-circuit time.

The lugs are secured to the cable core by a B-shaped crimp, and the sealing of the device is ensured by a 2nd hexagonal crimp, known as a shrink fit, on the cable sheath.
This crimping ensures that the sealing function is maintained over time, without the need for cable maintenance.
As the thimble is finished with a significant bend, the cable sheath is not damaged and remains intact over time.
/ Technical specifications
Penta Bulletpoint Product kind : Cable
Penta Bulletpoint Cable material : Copper
Penta Bulletpoint Cable isolation type : PVC
Product reference Isc Max (short-circuit current) kA/0.3s Isc Max (short-circuit current) kA/1.5s Isc Max (short-circuit current) kA/2s Isc Max (short-circuit current) kA/3s Short-circuit intensity kA/0.5s Short-circuit intensity kA/1s Technical sheet Quantity
Section câble de cc 10mm² 4,8 2,2 1,9 1,5 3,7 2,5
Pulse 32 Darkbg
Section câble de cc 120mm² 58 25,9 22,4 18,3 45 31,5
Pulse 32 Darkbg
Section câble de cc 150mm² 72,5 32,4 28,1 22,9 56 40
Pulse 32 Darkbg
Section câble de cc 16mm² 7,7 3,5 3 2,4 6 4
Pulse 32 Darkbg
Section câble de cc 25mm² 12 5,4 4,7 3,8 9,5 6,5
Pulse 32 Darkbg
Section câble de cc 35mm² 17 7,6 6,5 5,3 13 9
Pulse 32 Darkbg
Section câble de cc 40mm² 19,3 8,6 7,5 6,1 15 10,5
Pulse 32 Darkbg
Section câble de cc 50mm² 24 10,8 9,4 7,6 18,5 13
Pulse 32 Darkbg
Section câble de cc 70mm² 34 15,1 13,1 10,7 26 18,5
Pulse 32 Darkbg
Section câble de cc 75mm² 36 16,2 14 11,5 28 20
Pulse 32 Darkbg
Section câble de cc 95mm² 46 20,5 17,8 14,5 35,5 25
Pulse 32 Darkbg