Control and measurement advices
Control and measurement advices > TE-FR100

TE-FR100

Power socket tester, earth connection impedance meter
Technical sheet
Pulse 32 Darkbg
/ Standards
IEC 61557-1, IEC 61557-3, IEC 61010-1
/ Use

LV electrical systems must comply with the installation rules of standard NFC 15-100.

Compliance must be guaranteed upon initial commissioning, and also after periodic inspections.

In particular, the value of the EARTH CONNECTION must be inspected.

Tohm-e can measure that value from a simple power socket.

The device can also check if the socket is wired correctly (position of phase, neutral and earth).

/ Technical specifications

- Measurement using the earth loop principle

- Device designed for TT earth systems

- Earth connection measurement: 0.0 D to 2kD

- Voltage measurement: 50V to 440V (actual RMS value)

- Indication of the position of phase, neutral and earth

- Usage temperature: -20°C to +55°C

Advantages

• SIMPLE : just connect Tohm-e to a power socket.

• INSTANTANEOUS : the display is immediate

No risk of failure, as Tohm-e operates without cells.

• AUTOMATIC INTERPRETATION OF RESULT :

- blue screen showing that the earth value is OK (earth <100D)

- red screen showing that the earth value is not OK (earth >100D)

• ADAPTS TO ALL REQUIREMENTS : the rotating head allows easy reading