Temporary electrical insulation
Temporary electrical insulation > TE08

TE08

Insulating screen 20 kV for substation
Technical sheet
/ Use
Insulating panels to separate busbars, protective device to prevent MV switch-disconnectors from being closed, protective panel to separate working areas, insulating baseplate for transformer
/ Technical specifications

Material : fibreglass reinforced polyester

Fire classification : M3 self-extinguishing UL94V-0

Dielectric test : according to standard IEC 60243-1

Mechanical test : according to standard ISO 178/527/604/179 and 180

Colour : white.

Assembling of combined screens is done with insulating corner pieces (ref. TC144C) and bolts (ref. TC144B).

Dimensions (mm) Poids (kg) Modèle Description Technical sheet Quantity
2000 x 1000 x 3 11,8 Grand modèle Écran isolant 20 kV grand modèle pour postes
Pulse 32 Darkbg
1000 x 1000 x 3 5,9 Petit modèle Écran isolant 20 kV petit modèle pour postes
Pulse 32 Darkbg