Technical sheet
Pentagone Header Penta
/ BMT18-CAB
Grounding and short-circuiting device
See online technical sheet
/ Standards
Penta Bulletpoint CEI 61230
Penta Bulletpoint CEI 61138
/ Use
Grounding and shorting device for mt systems in bare conductors of mt/bt secondary substations - cylindrical conductors
- No. 3 light alloy pliers with spring clamping ø 3á20 mm
- No. 1 pliers holder head with recovery hook
- No. 2 copper cables sect. 35 mm2 L=2 m covered in silicone sheathing
- No. 1 copper ground cable sect. 16 mm2 L=6 m covered with silicone sheath
- No. 1 light alloy self-milling ground clamp with screw clamping thickness 0á40 mm
- No. 1 insulating foil L=2.2 m in two joinable parts with carrying bag and female quick coupler
/ Advantages
Penta Bulletpoint Robust
Penta Bulletpoint Guarantees safe action to prevent electrification
/ Areas of activity
Electrical distribution
Industry
Substation
Document not contractually binding, errors and omissions excepted
pentaesp.com
Logo Penta
Technical sheet
Pentagone Header Penta
/ Technical specifications
Penta BulletpointProduct specificity : Temporary
Penta BulletpointProduct kind : Dispositif
Penta BulletpointNozzle type : Innesto rapido maschio
Penta BulletpointClamp material : Lega leggera
Penta BulletpointClamp tightenning (mm) : 3á20
Penta BulletpointConductor type : Round
Penta BulletpointVise clamping capacity (mm) : 0á40
Penta BulletpointOperating voltage (V) : HTA (1 000 V to 50 000 V)
Penta BulletpointIsc Max (short-circuit current) kA/0.3s : 13.6
Penta BulletpointShort-circuit intensity kA/0.5s : 11.6
Penta BulletpointShort-circuit intensity kA/1s : 8.2
Penta BulletpointCable isolation type : Silicone
Penta BulletpointPhase câble
Penta BulletpointPhase cable number : 2
Penta BulletpointPhase(s) cable cross-section (mm²) : 35
Penta BulletpointPhase(s) cable length (m) : 2
Document not contractually binding, errors and omissions excepted