🖨️ Download as PDF
Technical sheet
Pentagone Header Penta
/ TP57
Leakage multimeter clamp
See online technical sheet
/ Standards
IEC 61010 - 1 / IEC 61010-2 / IEC 61010-2-032 CAT III 600 V
/ Use

The TP57 clamp-on meter is the ideal tool to detect insulation faults and untimely tripping of RCDs caused by leakage currents.

It also provides all the functions of a clamp-on multimeter.

/ Technical specifications

RMS measurement

- resolution : 10µA

- strong immunity to spurious currents : 70dB

- 50/60Hz harmonic filter

- current : 30µA to 100A AC

- AC/DC voltage : 0.1V to 600V

- frequency : 5Hz to 1kHz

- resistance : 0.1Ω to 1kΩ

- audible continuity : <35Ω

- backlit display : 10,000 counts

- functions : max. and Delta; display meomorization

- battery life indicator light, automatic power off

Supplied with 1 set of 4 mm diameter elbowed leads in red/black with 4 mm diameter contact points, 1 set of 2 x 1.5 V batteries (AAA or LR3) and  1 carrying case

Document not contractually binding, errors and omissions excepted
pentaesp.com
Logo Penta
Technical sheet
Pentagone Header Penta
Advantages

To check leakage currents quickly and locate insulation faults in live installations.

Document not contractually binding, errors and omissions excepted
pentaesp.com
Logo Penta