🖨️ Download as PDF
Technical sheet
Pentagone Header Penta
/ BTA800-5
Grounding and short-circuiting device of LV overhead lines
See online technical sheet
/ Standards
Penta Bulletpoint CEI 61230
Penta Bulletpoint CEI 61138
/ Use
Grounding and shorting of overhead lines in bare conductors spring clamps Ø 3á18 mm
- No. 5 light alloy clamps with spring clamping ø 3á18 mm integral with fiberglass foils with handle
- No. 4 copper cables sect. 16 mm2 L=0.8 m covered with silicone sheathing
- No. 1 copper ground cable sect. 16 mm2 L=14 m covered with silicone sheathing
- No. 1 earth electrode
- No. 1 reach collector
- No. 1 sheet metal container for storing and transporting the device
/ Advantages
Penta Bulletpoint Robust
Penta Bulletpoint Automatic spring clamp, no manual tightening required
/ Areas of activity
Electrical distribution
Industry
Substation
Transport
Document not contractually binding, errors and omissions excepted
pentaesp.com
Logo Penta
Technical sheet
Pentagone Header Penta
/ Technical specifications
Penta BulletpointProduct specificity : Temporary
Penta BulletpointProduct kind : Earthing equipment/kits
Penta BulletpointClamp material : Lega leggera
Penta BulletpointClamp tightenning (mm) : 3á18mm
Penta BulletpointConductor type : Round
Penta BulletpointVise clamping capacity (mm) : 3á18mm
Penta BulletpointOperating voltage (V) : BT (50 V to 1000 V)
Penta BulletpointField of use (environment) : Aerial or transformation station
Penta BulletpointWay of access : From the floor
Penta BulletpointShort-circuit intensity kA/0.5s : 5.7 kA
Penta BulletpointShort-circuit intensity kA/1s : 4.1 kA
Penta BulletpointCable material : Copper
Penta BulletpointCable isolation type : Silicone
Penta BulletpointPhase câble
Penta BulletpointPhase cable number : 4
Penta BulletpointPhase(s) cable cross-section (mm²) : 16
Document not contractually binding, errors and omissions excepted
pentaesp.com
Logo Penta