🖨️ Download as PDF
Technical sheet
Pentagone Header Penta
/ LW04-06
Mechanical restraint system
See online technical sheet
/ Use
The mechanical restraint device is used to mechanically shunt a damaged conductor, with cross-sections greater than or equal to 12 mm² (23 KCMIL), and less than 148 mm² (292 KCMIL). The device does not ensure electrical continuity. Under no circumstances does the mechanical restraint system replace a mechanical tension recovery device exemple Strap hoist or cable hoist.
One left and one right cable clamp with two ring screws and a screw jack take-up device
Overall dimensions: 390 x 65 x 220 mm / 1’ 3’’ x 2 5/9’’ x 8 2/3’’
Screw jack stroke: 30 mm / 1 1/6’’
Two flexible and two rigid, removable connecting rods
A locking hook with a hinged ring ref
A double clevis swivel
Document not contractually binding, errors and omissions excepted
pentaesp.com
Logo Penta
Technical sheet
Pentagone Header Penta
/ Technical specifications
Penta BulletpointOperating voltage (V) : HTA (1 000 V to 50 000 V)
Penta BulletpointCMU (daN) : 800
Penta BulletpointTightening torque (N.m) : 25
Document not contractually binding, errors and omissions excepted
pentaesp.com
Logo Penta
Technical sheet
Pentagone Header Penta
Product reference Lenght Weight (kg) Ø (mm)
LW04-06-SCD 390 mm 2,5 -
LW04-06-SCG 390 mm 2,5 -
LW04-06-TS-700 700 mm 0,3 8
LW04-06-TS-1250 1250 mm 0,4 8
LW04-06-TR-700 700 mm 0,4 15
LW04-06-TR-1250 1250 mm 0,7 15
LW04-06-EM 110 mm 0,2 40
LW04-06-CR 110 mm 0,5 -
Document not contractually binding, errors and omissions excepted
pentaesp.com
Logo Penta