/ ATL110
Grounding and short-circuiting device of substations at
See online technical sheet
/ Use
Electrical distribution, high voltage.
Grounding and short-circuiting of HV substations in flat bars, cylindrical conductors and spherical fixed points
No. 3 light alloy screw clamps with CH22 shank and clamping:
- ø 14÷70 mm on cylindrical conductors
- 20÷110 mm thick on flat bars
- 50÷120 mm thick on the inclined grip
- on spherical fixed points ø 25 mm
No. 3 copper cables sect. 95 mm2 L=9 m covered with silicone sheath
No. 3 brass ground clamps with screw clamps thickness 0÷35 mm and spherical fixed points
/ Advantages
Penta Bulletpoint High clamping capacity
/ Areas of activity
Electrical distribution
Industry
Substation
Document not contractually binding, errors and omissions excepted
pentaesp.com
Logo Penta
Technical sheet
Pentagone Header Penta
/ Technical specifications
Penta BulletpointProduct specificity : Temporary
Penta BulletpointProduct kind : Dispositif
Penta BulletpointClamp material : Brass
Penta BulletpointConductor type : Ball, Round, Flat
Penta BulletpointVise clamping capacity (mm) : 0÷35
Penta BulletpointOperating voltage (V) : HTB (> 50 000 V)
Penta BulletpointField of use (environment) : Cabina
Penta BulletpointIsc Max (short-circuit current) kA/0.3s : 40.4
Penta BulletpointShort-circuit intensity kA/0.5s : 35.6
Penta BulletpointShort-circuit intensity kA/1s : 25.2
Penta BulletpointCable material : Copper
Penta BulletpointCable isolation type : Silicone
Penta BulletpointPhase câble
Penta BulletpointPhase cable number : 3
Penta BulletpointPhase(s) cable cross-section (mm²) : 95
Penta BulletpointPhase(s) cable length (m) : 9