Technical sheet
Pentagone Header Penta
/ LW03-17
Insulator rubber skirts
See online technical sheet
/ Use
The skirts are mounted on the insulating tubes Ø 32, 39, 64 mm. / 1 1/4’’, 1 1/2’’, 2 1.
In the working position, the larger diameter part of the skirts must always face downwards.
In all cases, skirts must be used in pairs.
A pair of skirts consists of two skirts joined together.

Skirts are used:
to avoid the water flow along an insulating pole whilst working in wet conditions.
In this case, the pole is equipped with a pair of skirts.

The insulating tubes must be equipped with :
A pair of skirts, if the voltage of the network is 63 kV, 90 kV or 150 kV,
Two pairs of skirts, if this voltage is 225 kV or 400 kV.
Note: The skirt fitting tool must be coated with silicone grease before fitting the skirts.
/ Areas of activity
Transport
Document not contractually binding, errors and omissions excepted
pentaesp.com
Logo Penta
Technical sheet
Pentagone Header Penta
/ Technical specifications
Penta BulletpointPole kind : Pole accessories
Penta BulletpointWork type : Live working
Penta BulletpointOperating voltage (V) : HTB (> 50 000 V)
Document not contractually binding, errors and omissions excepted
pentaesp.com
Logo Penta
Technical sheet
Pentagone Header Penta
Product reference Pipe diameter (mm) Pipe diameter (inch) Accessory weight (kg) Diameter(s) (mm) Accessory weights (lbs) Accessory type
LW03-17-J-32 32 1''1/4 0.04 int: 30 - ext: 70 0.1 Jupe
LW03-17-J-39 39 1''1/2 0.02 int: 35 - ext: 70 0.1 Jupe
LW03-17-J-64 64 2''1/2 0.12 int: 60 - ext: 121 0.3 Jupe
LW03-17-OPJ-32 32 1''1/4 0.4 55 0.9 Outil de pose
LW03-17-OPJ-39 39 1''1/2 0.45 55 1.0 Outil de pose
LW03-17-OPJ-64 64 2''1/2 1.1 78 2.4 Outil de pose