🖨️ Download as PDF
Technical sheet
Pentagone Header Penta
/ AMT50
Grounding and short-circuit device for MV substations and electrical stations with universal contact clamps
See online technical sheet
/ Standards
Penta Bulletpoint CEI 61230
Penta Bulletpoint CEI 61138
/ Use
-n°3 Aluminium universal contact clamp, tested for high currents. CH12 hexagonal shank, for insertion on EF-type shank, and steel clamping screw protected with antioxidant galvanic treatment.
Clamping capacity:
-cylindrical conductors diameter 5 - 40 mm;
-flat bars 40 x 60 mm;
-Board bars 12 x 60 mm;
-45° inclined bars up to 28 mm.
-n°3 extra-flexible short-circuit cables made of electrolytic copper coated with a transparent sheath, for connection between the clamps and the central connector. Cross-section 70 mm², length 0.75 m, complete at the ends with tinned electrolytic copper cable lugs and additional transparent heat shrink tubing reinforcement.
-Three-pin connector. -Earth cable, length 2 m.
-Earth clamp, clamping capacity up to 22 mm.
-Insulation strap made of glass-fibre reinforced vinylester resin tubing for operating contact clamps, length 1.35 m in two elements with quick-connect fitting.
- Sturdy canvas bag for containing and transporting the device and foil.
/ Advantages
Penta Bulletpoint Allows clamp to be positioned and tightened horizontally on anchored conductors
/ Areas of activity
Electrical distribution
Industry
Electric traction
Document not contractually binding, errors and omissions excepted
pentaesp.com
Logo Penta
Technical sheet
Pentagone Header Penta
/ Technical specifications
Penta BulletpointProduct specificity : Temporary
Penta BulletpointProduct kind : Dispositif
Penta BulletpointClamp material : Brass
Penta BulletpointConductor type : Round, Flat
Penta BulletpointVise clamping capacity (mm) : Fino a 22
Penta BulletpointOperating voltage (V) : HTA (1 000 V to 50 000 V)
Penta BulletpointIsc Max (short-circuit current) kA/0.3s : 29.3
Penta BulletpointShort-circuit intensity kA/0.5s : 23.5
Penta BulletpointShort-circuit intensity kA/1s : 16.6
Penta BulletpointCable material : Copper
Penta BulletpointCable isolation type : PVC
Penta BulletpointPhase câble
Penta BulletpointPhase cable number : 3
Penta BulletpointPhase(s) cable cross-section (mm²) : 70
Penta BulletpointPhase(s) cable length (m) : 0.75
Penta BulletpointFloor cable