🖨️ Download as PDF
Technical sheet
Pentagone Header Penta
/ TAG330
Voltage detector TAG330
See online technical sheet
/ Standards
Penta Bulletpoint IEC 61243-1: VOLTAGE DETECTORS CAPACITIVE TYPE TO BE USED FOR VOLTAGES EXCEEDING 1 kV A.C
Penta Bulletpoint CE compliante
/ Use
• Device designed to test the absence of nominal voltage on HV systems from 50 kV to 765 kV.
• It will detect any nominal voltage present on networks or substation and must not detect induced voltages in order to allow the grounding operation.
electrical-detection / TAG330 📁 / penta-catchprase-complement
/ Advantages
Penta Bulletpoint This original configuration adapted to VHV and giving very high performances in the case of high induction and electric fields disturbance.
Penta Bulletpoint Design adopted by our most demanding users.
Penta Bulletpoint Protected circuit Board.
Penta Bulletpoint Glossy PC housing for easy cleaning.
Penta Bulletpoint Self test by Voltage injection on probe socket.
Penta Bulletpoint Test of battery level and threshold stability.
/ Areas of activity
Production
Substation
Transport
Document not contractually binding, errors and omissions excepted
pentaesp.com
Logo Penta
Technical sheet
Pentagone Header Penta
/ Technical specifications
Penta BulletpointPower type : Alternating power
Penta BulletpointCondition of use : Outside
Penta BulletpointTemperature of use (C°) : -25...+55
Penta BulletpointHymidity (Max) (%) : 96
Penta BulletpointBattery type : 9V battery (x1)
Penta BulletpointConnector type : Universal (U)
Penta BulletpointCase material : Polycarbonate
Penta BulletpointMeasurement (mm) : 215 x 90 x 90
Penta BulletpointWeight (kg) : 0,529
Penta BulletpointPackaging : Metal case
Voltage presence indication
Acces battery
Soft case
Document not contractually binding, errors and omissions excepted
pentaesp.com
Logo Penta
Technical sheet
Pentagone Header Penta
/ Table legend
Altre regolazioni disponibili in rapporti di 1/3 fino a 735 kV.
Product reference Voltage range Network frequency (Hz) Color Notice Electrode type (mm)
330F060090C5 60-90 50 Yellow PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F150150C5 150 50 Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F225400C5 225-400 50 Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F400765C5 400-765 50 Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F033132C5 33-132 50 Red PACK F (FR/GB/DE/ES/PT/PL) V56, AC60, AC120, D100
330F033132C6 33-132 60V Red PACK F (FR/GB/DE/ES/PT/PL) V56, AC60, AC120, D100
330F050090C5 50-90 50 Yellow PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F050090C6 50-90 60V Yellow PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F055070C5 55-70 50 Yellow PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F060090C6 60-90 60V Yellow PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F060150C5 60-150 50 Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F060150C6 60-150 60V Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F060220C5 60-220 50 Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
Document not contractually binding, errors and omissions excepted
pentaesp.com
Logo Penta
Technical sheet
Pentagone Header Penta
Product reference Voltage range Network frequency (Hz) Color Notice Electrode type (mm)
330F060220C6 60-220 60V Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F090225C5 90-225 50 Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F090225C6 90-225 60V Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F110275C5 110-275 50 Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F132500C5 132-500 50 Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F150150C6 150 60V Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F150420C5 150-420 50 Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F150420C6 150-420 60V Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F220400C5 220-400 50 Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F220400C6 220-400 60V Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F220500C5 220-500 50 Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F220500C6 220-500 60V Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F225400C6 225-400 60V Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F400765C6 400-765 60V Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F044132C5 44-132 50 Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F060110C5 60-110 50 Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
Document not contractually binding, errors and omissions excepted
pentaesp.com
Logo Penta
Technical sheet
Pentagone Header Penta
Product reference Voltage range Network frequency (Hz) Color Notice Electrode type (mm)
330F060225C5 60-225 50 Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F066132C5 66-132 50 Red PACK F (FR/GB/DE/ES/PT/PL) V56, AC60, AC120, D100
330F080110C5 80-110 50 Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F088132C5 88-132 50 Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330F110150C5 110-150 50 Red PACK F (FR/GB/DE/ES/PT/PL) AC60, AC120, D100
330G060090C5 60-90 50 Yellow PACK G (GB/GR/NL/BG/IT/AR/TR) AC60, AC120, D100
330G060090C6 60-90 60V Yellow PACK G (GB/GR/NL/BG/IT/AR/TR) AC60, AC120, D100
330G060150C5 60-150 50 Red PACK G (GB/GR/NL/BG/IT/AR/TR) AC60, AC120, D100
330G090225C5 90-225 50 Red PACK G (GB/GR/NL/BG/IT/AR/TR) AC60, AC120, D100
330G090225C6 90-225 60V Red PACK G (GB/GR/NL/BG/IT/AR/TR) AC60, AC120, D100
330G150150C5 150 50 Red PACK G (GB/GR/NL/BG/IT/AR/TR) AC60, AC120, D100
330G150150C6 150 60V Red PACK G (GB/GR/NL/BG/IT/AR/TR) AC60, AC120, D100
330G225400C5 225-400 50 Red PACK G (GB/GR/NL/BG/IT/AR/TR) AC60, AC120, D100
330G225400C6 225-400 60V Red PACK G (GB/GR/NL/BG/IT/AR/TR) AC60, AC120, D100
330G400765C5 400-765 50 Red PACK G (GB/GR/NL/BG/IT/AR/TR) AC60, AC120, D100
330G400765C6 400-765 60V Red PACK G (GB/GR/NL/BG/IT/AR/TR) AC60, AC120, D100
Document not contractually binding, errors and omissions excepted
pentaesp.com
Logo Penta
Technical sheet
Pentagone Header Penta
Product reference Voltage range Network frequency (Hz) Color Notice Electrode type (mm)
330G060150C6 60-150 60V Red PACK G (GB/GR/NL/BG/IT/AR/TR) AC60, AC120, D100
330G060220C5 60-220 50 Red PACK G (GB/GR/NL/BG/IT/AR/TR) AC60, AC120, D100
330G060220C6 60-220 60V Red PACK G (GB/GR/NL/BG/IT/AR/TR) AC60, AC120, D100
330G132500C5 132-500 50 Red PACK G (GB/GR/NL/BG/IT/AR/TR) AC60, AC120, D100
330G132500C6 132-500 60V Red PACK G (GB/GR/NL/BG/IT/AR/TR) AC60, AC120, D100
330G150420C5 150-420 50 Red PACK G (GB/GR/NL/BG/IT/AR/TR) AC60, AC120, D100
330G150420C6 150-420 60V Red PACK G (GB/GR/NL/BG/IT/AR/TR) AC60, AC120, D100
330G220500C5 220-500 50 Red PACK G (GB/GR/NL/BG/IT/AR/TR) AC60, AC120, D100
330G220500C6 220-500 60V Red PACK G (GB/GR/NL/BG/IT/AR/TR) AC60, AC120, D100
Document not contractually binding, errors and omissions excepted