Grounding, short-circuit and equipotentiality device MV
See online technical sheet
/ Standards
CEI 61230
CEI 61138
/ Use
Device for grounding and short-circuiting and equipotentiality of mt terminals in the transition from overhead mt lines in bare conductors to MV lines in cable
/ Advantages
Robust
Allows clamp to be positioned and tightened horizontally on anchored conductors
/ Areas of activity
Electrical distribution
Industry
Electric traction
Technical sheet
/ Technical specifications
Product specificity
:
Temporary
Product kind
:
Dispositif
Clamp tightenning (mm)
:
3á20
Conductor type
:
Round, Flat
Conductor diameter
:
3á18
Operating voltage (V)
:
HTA (1 000 V to 50 000 V)
Field of use (environment)
:
Way of access
:
From the floor
Isc Max (short-circuit current) kA/0.3s
:
11.1
Short-circuit intensity kA/0.5s
:
8.8
Short-circuit intensity kA/1s
:
6.2
Composition
:
n° 1 pinza in lega leggera con serraggio a molla ø 3á20 mm n° 3 pinze in lega leggera orientabili con serraggio a vite a codolo esagonale DIN con presa: - ø 3á18 mm su conduttori cilindrici - spess. Max 60x12 mm su barre piatte n° 1 testina di manovra DIN n° 1 piattello portapinze n° 1 gancio di recupero in acciaio inox n° 2 cavi in rame sez. 16 mm2 L=4 m ricoperti in guaina siliconica n° 2 cavi in rame sez. 25 mm2 L=2 m ricoperti in guaina siliconica n° 1 fioretto isolante in 2 elementi L= 1m + 0,6 m (lunghezza totale 1,6 m) assiemabili con giunto simplex completo di sacca in tela nylon n° 1 stafa portapinze