IEC 61243-1: VOLTAGE DETECTORS CAPACITIVE TYPE TO BE USED FOR VOLTAGES EXCEEDING 1 kV A.C
CE compliante
Loud indication sound (100 dB at 1m).
The visual indication is visible in all positions
Direct access to the battery and sealed electronics compartment (IP65)
Permanent standby status with automatic wake up function
The presence of voltage within the calibrated range or above is indicated by a RED light and a beeping sound
The self test checks all the circuits, the reference detection level and the battery voltage
Self test OK: The OK status (ready for use) of the device is indicated by a GREEN light
The “ready for use” state is indicated by the green indication for 2 minutes
A low battery level is indicated by an ORANGE light
Removable and interchangeable stick end fitting
Electrical distribution
Industry
Production
Substation
Electric traction
Transport
Power type
:
AC Voltage
Network frequency (Hz)
:
50/60
Voltage range
:
15-45
Use condition
:
Indoor, Outdoor
Temperature of use (C°)
:
-25...+55
Hymidity (Max) (%)
:
96
Battery type
:
9V battery (x1)
End fitting
:
Universal (U), APV
Electrode type (mm)
:
V56
Case material
:
Polycarbonate
Color
:
Yellow
Dimensions (mm)
:
280 x 59 x 59
Weight (kg)
:
0.390
Acoustic sound level (dB)
:
100 dB
User's Manual
:
PACK F (FR/GB/DE/ES/PT/PL)
Packaging
:
Soft case with conductive lining for EMC protection