IEC 61243-1: VOLTAGE DETECTORS CAPACITIVE TYPE TO BE USED FOR VOLTAGES EXCEEDING 1 kV A.C
CE compliante
/ Use
This Go NoGo Contact voltage detector is designed for “proving dead”, making sure that nominal voltage is actually absent on a circuit of an HV distribution system, It’s two or three operating ranges are calibrated according to IEC recommendations between 1 kV and 69 kV:
• The device will detect any nominal voltage in contact with the part of the installation to be tested on overhead lines and substations. • It will not indicate voltage presence when detecting induced voltages in order to allow grounding operations.
/ Advantages
This multi range detector acts as up to 3 voltage detectors with 3 separated ranges: lower range, median range and upper range.
Loud indication sound (the 100 dB at 1m)
The visual indication is visible in all positions
Direct access to the battery and sealed electronics compartment (IP65)
Permanent standby status with automatic wake up function
The presence of voltage within the calibrated range or above is indicated by a RED light and abeeping sound
Self test OK the OK status (ready for use) of the device is indicated by a GREEN light
The self test checks all the circuits, the reference detection level and the battery voltage
The “ready for use” state is indicated by the green indication for 2 minutes
A low battery level is indicated by an ORANGE light
/ Areas of activity
Electrical distribution
Industry
Production
Substation
Electric traction
Transport
Technical sheet
/ Technical specifications
Power type
:
Alternating power
Network frequency (Hz)
:
50/60
1st voltage range (HV)
:
6-20
2nd voltage range (HV)
:
30-69
Condition of use
:
Inside, Outside
Temperature of use (C°)
:
-25...+55
Hymidity (Max) (%)
:
96
Battery type
:
9V battery (x1)
Connector type
:
Universal (U), APV
Electrode type (mm)
:
V56
Case material
:
Polycarbonate
Color
:
Yellow
Measurement (mm)
:
280 x 59 x 59
Weight (kg)
:
0,390
Notice
:
PACK F (FR/GB/DE/ES/PT/PL)
Packaging
:
Soft case with conductive lining for EMC protection
Acces battery
Voltage range selection
Voltage presence indication / No voltage indication